Dew Point Sensor

The Dew Point Sensor S217 provides reliable and long-term stable dew point measurement for demanding industrial applications. Its newly developed sensor element ensures accurate and consistent signal output, even in harsh environments, making it ideal for dew point monitoring in desiccant and refrigerated dryers.
The measured value is transmitted through a loop-powered 4–20 mA output, and the sensor parameters—such as analog output range and measuring units—can be easily configured using the service software package.

Product Detail

The S217-OEM dew point sensor combines compact design, robust housing, and flexible installation options. The device can be directly mounted on dryers via a G ½” thread connection, ensuring easy integration into existing systems.
With its stainless-steel filter cap and IP65 protection, the sensor offers excellent durability and resistance to dust, moisture, and condensation. The unit supports 2-wire or 3-wire 4–20 mA outputs, enabling compatibility with a wide range of industrial control systems.

Product Features

  • Compact design, easy to install on dryers or process lines
  • Wide measuring range down to –80 °C (customizable upon request)
  • Fast response time, providing quick indication when dew point exceeds the set range
  • Condensation resistant for reliable measurement stability
  • Non-corrosive gas compatibility, suitable for compressed air and inert gases

Technical parameters

Parameter Description
Measuring Range Customizable, –80 °C ~ +20 °C
Accuracy ±1 °C (–5 °C ~ +10 °C);
±2 °C (–50 °C ~ +20 °C);
> ±2 °C (other ranges)
Pressure Range –0.1 ~ 5.0 MPa
Power Supply 12 ~30 V DC
Measured Gas Non-corrosive gases
Ambient Temperature –10 °C ~ +50 °C
Transport Temperature –30 °C ~ +70 °C
Response Time (t90 @ 4 L/min) –40 °C → –20 °C: 20 s;
0 °C → –40 °C: 120 s
Output Signal 4–20 mA, 2-wire or 3-wire
Cable Connection M8 connector, 2 m open-end cable, 4-core
Housing Material Connector: Stainless Steel; Body: Aluminum Alloy
Protection Class IP65
Process Connection G ½” thread (ISO 228/1)
Sensor Protection Stainless-steel filter cap, pore size < 30 μm
EMC Compliance IEC 61326-1
Calibration Conditions Ambient 23 ± 3 °C; Humidity < 95 % RH (non-condensing); Gas flow > 1 L/min

Model

S217

Scroll to Top